Fire Safety Ventilation
In a fire emergency, stairwells are the primary escape route for building occupants. If smoke infiltrates these stairwells, visibility drops, breathing becomes difficult, and safe evacuation is compromised. A stair pressurisation system actively prevents this by forcing clean outside air into the stairwell at a higher pressure than the surrounding areas, creating a barrier that smoke cannot cross.
We design, install, and commission stair pressurisation systems that meet NCC and AS 1668.1 fire safety requirements for Class 2-9 buildings across Sydney. Our systems are engineered for each building’s specific configuration, including pressure relief dampers, variable-speed fans, and intelligent controls that modulate airflow based on how many doors are open during evacuation. Every installation includes full testing under simulated fire conditions, pressure differential verification, and complete compliance documentation for building certification and annual fire safety statements.




A stair pressurisation system has one job. Keep smoke out of the stair so people can leave and firefighters can get in. It is not a comfort system and it is not forgiving of shortcuts, because the only day it is tested for real is the day it has to work. We design, install and commission stair pressurisation across Sydney for residential towers, commercial buildings and mixed use developments, working with the fire engineer and certifier from the design stage rather than arriving at the end to make something fit.
A dedicated supply fan injects outside air into the stair, and the stair is held at a higher pressure than the adjacent fire affected floor. Smoke cannot push against that pressure, so it stays out of the escape route. The difficulty is not producing pressure. It is producing exactly the right amount of it. Too little and smoke leaks in. Too much and elderly occupants cannot open the door. That balance is the whole engineering problem, and it is won or lost in the details.
| Factor | Why it drives the outcome |
|---|---|
| Number of storeys | Taller buildings have more door gaps and leakage paths to overcome |
| Door leakage area | Gap around each door is the main loss, and it accumulates with height |
| Door opening force limit | Sets the ceiling on pressure, because the door has to remain usable |
| Stair construction | Sealed concrete and unsealed shafts behave completely differently |
| Openings to the stair | Open balconies, connecting bridges and roof access all change the calculation |
| Adjacent spaces | The pressure relationship to the fire floor and any vestibule matters |
Pressure disappears through gaps, and there are more of them than anyone expects. Door undercuts, gaps around frames, cable penetrations that were sealed loosely, and the top of a shaft that was never intended as an opening. We walk the stair core during design and again before commissioning, because adding fan capacity to overcome leakage is more expensive than closing the gap.
Once the fan is running there has to be a way for excess pressure to escape, otherwise the doors become too heavy to open and the system fails in a different direction. Relief paths, barometric relief dampers or pressure controlled relief all have their place. The point is that the system has to work with doors open as well as closed, and with the fire on the level that was never the one they tested on paper.
Smoke detection up to the fire alarm system triggers the mode change, the fan starts, and the system has to reach its design pressure quickly. We test the sequence with the fire contractor and document the response, because a fan that starts but takes too long to pressurise is treated the same as one that never started.
Commissioning is where a stair pressurisation system proves itself. We measure the pressure differential across the stair and the fire floor, check door opening forces with a gauge rather than by feel, and record the results for the certifier. After handover, the system needs regular testing on the schedule the building’s fire compliance requires, and annual servicing keeps it defensible. Both live inside the wider commercial ventilation Sydney package for most buildings.
Stair pressurisation is part of the smoke control strategy, which also covers the car park supply systems Sydney below and the jet fan installation Sydney used for distributing air through low ceiling car parks. The rest of the mechanical package is coordinated through commercial air conditioning Sydney and, on new builds, through construction air conditioning Sydney. For the broader ventilation design behind it, start with mechanical ventilation systems Sydney, or for the wider range see air conditioning in Sydney.
What developers, builders and strata managers ask us most about stair pressurisation.
A stair pressurisation system uses a dedicated supply fan to hold the stairwell at a higher air pressure than the fire affected floor. Because smoke cannot travel against that pressure difference, the escape route stays tenable for occupants leaving and for firefighters entering. The system includes the fan, ductwork or riser from outside air, relief arrangements, pressure or door sensors, and controls that trigger from the fire detection system. It is treated as part of the building’s smoke control strategy.