E3 is low pressure protection. Suction pressure fell below what the system needs and it stopped rather than run the compressor at a temperature it cannot survive. In practice that comes from one of two places: the circuit does not hold enough refrigerant, or the indoor coil is not picking up enough heat because the air across it is restricted.
Less refrigerant in the circuit means less for the compressor to work with, so suction pressure drops until protection opens. Refrigerant is a sealed charge that does not get used up, so a shortfall always means it has escaped somewhere. A unit that needs gas each season is telling you it has a leak worth finding.
Flares, brazed joints, Schrader cores and the coil are where leaks concentrate. Vibration loosens flares over years, poor brazing leaves porosity, and corrosion eats copper where it sits against a damp surface. Some leaks only show once the system is at operating temperature, which is why a cold test can miss them.
A pressure sensor that has drifted will report low pressure on a system holding a correct charge. Because the reading is electrical and the pressure is physical, the two are compared directly with a gauge on the same port. That comparison takes minutes and saves a recharge that was never needed.
Suction pressure and superheat are read together and compared with the manufacturer table for the day outdoor temperature. Reading pressure alone is unreliable because it moves with ambient. If the charge is short, the leak gets found before any gas is added, so the fault does not simply come back.
An electronic detector is run over every joint, with particular attention on flares, Schrader cores and the indoor coil. Where nothing shows, the circuit is isolated and pressure tested with dry nitrogen and left to stand. The pressure drop proves there is a leak; the detector is what finds its location.
The sensor is compared against a gauge on the same service port while the system runs. A reading that diverges, or one that stays flat while pressure changes, confirms the sensor. The plug and lead are checked at the same time, because a corroded connector produces exactly the same symptom as a failed sensor.