E1 is high pressure protection. Refrigerant pressure climbed past the limit the system will tolerate and it shut down to protect the compressor. The switch did its job, and the real question is what raised the pressure. Fujitsu splits usually get there because the outdoor coil cannot reject heat, or because something in the circuit is holding pressure where it should not.
The outdoor coil sits in the dirtiest position in the system, taking grass, pollen, leaves and whatever the wind brings. Once the fins are blocked, air cannot pass, heat cannot leave, and head pressure climbs until protection opens. Indoor coil condition matters too in heating mode, when it becomes the condenser.
A short charge producing high pressure seems contradictory until you look at what it does to coil temperatures. With less refrigerant circulating, the coil runs unevenly and the compressor works against pressures it was not designed for. This is why charge is measured rather than assumed when a high pressure code appears.
The pressure sensor can fail and report a trip that never happened. That is the diagnosis of elimination: once the coils are clean, the airflow is right and the charge is measured as correct, the sensor becomes the likely answer. Changing it before those checks is how a healthy system ends up with a new part.
The outdoor coil is checked from both sides, because the face can look clean while the back is packed solid. A soft brush and coil cleaner are used rather than a pressure washer, which bends fins and makes the airflow worse. The indoor filter and coil are checked at the same time for the heating case.
Charge is verified by subcooling and superheat against the figures for the outdoor temperature, not by a single gauge reading. If it is short, the leak search comes first. Topping up a system with a leak buys a season at most and leaves the same E1 waiting at the end of it.
A gauge is connected to the same port the sensor reads and the two are compared while the system runs. A sensor that does not track the gauge, or a switch that opens at the wrong pressure, has failed. That comparison is quick, costs nothing and prevents a part being ordered for a system that was fine.