E0 points at the outdoor unit control board. That board runs the compressor, the outdoor fan, the expansion valve and the signal back to the indoor unit, so a fault in it can bring the whole system down rather than just degrade performance. On a Fujitsu split the outdoor board also lives in the harshest position on the property, which is why it fails more often than the indoor one.
The board sits behind the panel that takes the sun, the rain and the salt air. Its relays switch the compressor current and its terminals carry the supply. A board that has lost an output or a sensing circuit will report E0 while the rest of it looks perfectly normal, which is why testing the outputs matters more than looking at it.
A surge through the supply can damage the low voltage side of the board without leaving any visible mark. So can a compressor contactor that arcs as it opens. These faults tend to appear after a storm or after other electrical work on the property, and the board is usually the casualty rather than the cause.
The harness between the boards and the outdoor components passes close to the casing and the compressor compartment. Heat hardens the insulation, vibration rubs it through, and rodents find the warm space attractive. A conductor shorting against the casing will produce E0 and can damage the board it connects to.
Isolate the outdoor unit for a full five to ten minutes, because a protection trip on the board is designed to latch. Restore power and watch the restart. A board that comes back cleanly handled a transient event. One that trips again within minutes is failing, and repeated resets risk taking other components with it.
With the power off and the panel removed, the board is examined for burnt tracks, swollen capacitors, corrosion across the pins and any sign of water or insect ingress. Anything visible means replacement. A board that looks clean still needs its outputs measured, because appearance alone clears nothing.
Every plug on the outdoor board is released, inspected for corrosion and reseated. The harness is followed for a rub where it passes the casing edge or the compressor compartment. Each conductor is continuity tested and checked for a short to earth. On an intermittent E0 this usually finds the fault.
Replacing an outdoor board is a straightforward job, but the checks around it are not. Before a new board goes in, the compressor, the fan motors and the supply have to be confirmed sound, because a fault elsewhere can destroy the replacement on its first start. That is the step that protects the cost of the part.