A6 means the indoor unit’s fan motor is not doing what the board asked of it. The board watches the motor and expects a speed signal back, and when that signal is missing or wrong the unit stops to protect the motor and the coil. The result is a head that runs but moves no air, or one that stops shortly after starting.
The indoor fan runs continuously for years, and the bearings and windings eventually give up. A motor on its way out often starts with a rumble or a slow start before it stops reporting speed and trips A6. Motors on older units are the usual candidates, particularly where the unit has run on a dirty filter for a long stretch.
A blade fouled with dust, or one that has something caught in it, loads the motor until it can no longer hold speed. The board sees the discrepancy and trips A6. Check it before condemning the motor, because a clean is a fraction of the cost. Broken or cracked blades are a replacement, not a clean.
The motor harness runs from the board to the fan, and it can be pinched during a service, chewed by rodents or corroded at the plug. A loose plug gives an intermittent A6 that comes and goes with vibration. Continuity and plug condition are checked before the motor is blamed, because the harness is far cheaper.
A motor working too hard, or one with a failing bearing, will run hot and then cut out on its internal protection. A6 often appears after the unit has been running a while rather than at startup, which is the clue. If the motor is hot to touch and the blade turns stiffly by hand, the bearing is the problem.
A fan that is not turning while the compressor runs will freeze the indoor coil or overheat the outdoor unit depending on the mode. Isolate the system at the isolator and leave it off until the fan is checked. Running it to see whether the code clears risks the compressor for no gain.
With the power off, the barrel or blade is turned by hand. It should move freely with no rubbing and no play in the shaft. Anything caught in it is removed and any dust matting is cleaned off. A blade that grinds or wobbles points at the bearing or the blade rather than the board.
After the unit has run, the motor body is checked for heat that is out of proportion to the run time. A motor that is hot after a few minutes has a bearing or winding problem. Checking it cold tells you nothing, which is why this test happens after a run rather than before.
The harness between the board and the motor is traced end to end, looking for crushed sections, rodent damage and corrosion at the plugs. Each connector is reseated. On units with a speed feedback wire, that conductor gets particular attention, because a break there gives a motor fault code on a healthy motor.